Step 1: define what you control
| Objective | Use when | Example |
|---|---|---|
| RH at a stated temperature | Materials, comfort, storage | Warehouse at 50 % RH, 20 °C |
| Dew point | Condensation on cold surfaces | Electrical cabinet, cold store dock |
| Material moisture | Drying | Water-damaged structure, slab |
| Biological or quality outcome | Mould, disease, shelf life | Greenhouse crops, food storage |
A space can hold 50 % RH and still condense on a chilled surface. Choose the variable that matches the risk; see dehumidifier settings for mould prevention.
Step 2: calculate the moisture load
Add the moisture sources that occur together in the sizing period. Count outdoor ventilation, uncontrolled air entering through doors and leaks, and moisture released by people, products or work such as washdown. Give ventilation air credit for any drying that already happens upstream. Count each airflow once.
Worked warehouse example. The warehouse receives 2,000 m³/h of outdoor air at 25 °C and 70% RH. The indoor target is 20 °C and 60% RH. At standard atmospheric pressure, the humidity ratios are about 13.9 and 8.7 g of water per kg of dry air, respectively. The ventilation load is about 12.0 kg/h (2,000 m³/h × 1.16 kg dry air/m³ × 0.0052 kg water/kg dry air).
| Moisture source during the design period | Removal needed |
|---|---|
| Outdoor ventilation, calculated above | 12.0 kg/h |
| Additional air entering through loading doors, example allowance | 2.0 kg/h |
| Internal sources during the same period, example allowance | 1.0 kg/h |
| Total design load for the example | 15.0 kg/h |
Use the hourly load for selection. The combined load would represent 360 kg of water over 24 hours if it stayed at 15 kg/h throughout. For recovery after a long shutdown or wet cleanup, check separately how much extra water must be removed and how soon the space must return to target. See commercial dehumidifier sizing.
Step 3: set the design operating condition
Ask each supplier for the removal rate at the temperature and RH of the air actually entering its unit. For a unit taking return air from the example warehouse, start with 20 °C and 60% RH. For a unit taking mixed outdoor and return air, calculate the mixed inlet condition. Check a colder or drier operating point if the equipment also has to hold the target under those conditions.
Two catalogue ratings show why the inlet condition matters. The refrigerant RYCF-22S is rated at 480 L/day at 30 °C and 80% RH. The desiccant RY-1500M is rated at 240 L/day at 20 °C and 60% RH, equivalent to about 10 kg/h of water removal at that rating point. Request the RYCF-22S removal rate at the warehouse inlet condition before comparing capacity. Ask what airflow, external static pressure and, where applicable, defrost or reactivation conditions the selection assumes. See what a daily removal rating means.
Step 4: refrigerant or desiccant
| Condition | Usual route |
|---|---|
| Warm, moderate RH target | Refrigerant |
| Cold space, or dew point below about 5 °C | Desiccant |
| Warm, high load, very low dew point | Refrigerant + desiccant |
Step 5: choose the format
| Format | Suits |
|---|---|
| Portable | Temporary, restoration, small spaces |
| Floor-standing industrial | Warehouses, workshops |
| Ceiling-mounted | Floor space limited; greenhouses, food plants |
| Ducted | Even distribution; plant rooms; pools |
For temporary drying, compare commercial portable dehumidifiers. For permanent warehouse installations, see warehouse dehumidifiers. For a ducted installation, compare industrial ceiling dehumidifiers and request the unit’s airflow at the external static pressure calculated for your duct layout.
Step 6: unit count from capacity and distribution
Divide the concurrent load by each unit’s removal rate at the design inlet condition, then round up. In the warehouse example, 15 kg/h ÷ 10 kg/h per RY-1500M = 1.5, so the rated capacity gives a starting count of two duty units for that desiccant option. This assumes both units deliver the rated 10 kg/h in the installed configuration. A two-unit refrigerant option needs at least 7.5 kg/h per unit at 20 °C and 60% RH to cover the same load, before any agreed margin.
Then check the air path. Lay out supply and return routes so air reaches each aisle and zone, with particular attention to racks, partitions and loading doors. If the project must carry the full load with one unit off, the two-duty-unit example needs three units in total at the same per-unit capacity. See large commercial dehumidifiers.
Step 7: installation
Check the installation before placing the order. For the warehouse, mark equipment positions, aisle clearances and service access on the layout. Confirm voltage, phase and electrical load for the chosen configuration. For ducted units, check delivered airflow at the calculated external static pressure and confirm there is room to replace filters and service the equipment.
For refrigerant units, plan a gravity drain or pump and test the discharge route under flow. For a desiccant unit, check the reactivation air supply and wet-air exhaust routing, along with the effect on room pressure and heat load. If those air paths change the amount of outdoor air entering the warehouse, revisit the moisture balance. See condensate pump planning.
Step 8: controls and monitoring
Measure humidity where it represents the protected stock and how the space is used. For the warehouse, use a representative storage aisle as a control point and spot-check a harder-to-reach aisle or the storage zone near the loading doors. Keep the control sensor clear of the unit’s dry-air discharge.
Write down when each unit starts and stops, how the lead and lag units are staged, and how alarms reach staff. Confirm the points that the selected controller or building management system exposes. Include high humidity, unit faults and any fitted condensate pump or high-water alarm in the test plan.
Step 9: acceptance and verification
Agree the acceptance limits and test period before installation. For the example warehouse, specify where and when to check the 20 °C and 60% RH target, the permitted excursions, and the recovery time after a representative loading-door cycle. Log temperature and RH at the agreed storage points through a normal shift and a demanding period. Record door activity and unit states so the trend can be tied to what was happening on site.
At handover, check airflow to the agreed zones, prove the sequence and installed alarms, and test drainage or reactivation operation for the selected equipment. Save the trend and settings as the baseline for the maintenance checklist.
Information to prepare
Space and use, target, moisture sources, ventilation, temperature range, preferred format, power, drainage, controls, schedule. Send to us via our industrial dehumidifiers page.
FAQ
Frequently asked questions
How do I choose a commercial dehumidifier?
Define the target, calculate the load, set the design condition, choose technology and format, then size the count at that condition.
What size commercial dehumidifier do I need?
Enough capacity at your operating condition to remove the moisture load in the demanding period.
Why does my dehumidifier underperform its rating?
Ratings are at warm, humid test conditions; at cooler or drier inlet conditions, capacity is lower.
Sources
- ASHRAE Handbook—Fundamentals, Psychrometrics; HVAC Systems and Equipment, Dehumidification.