EKS-HUM-013 / Moisture load and airflow

Moisture Load

湿负荷

Moisture load is the rate at which water vapour must be removed from a defined space or process to maintain the selected humidity condition.

Aliases
water-vapour load, humidity load

QUANTITY, SYMBOL AND UNIT

Quantity / objectMoisture load rate
Symbolṁ_w,load
SIkg/skilogram of water per second
Commonkg/hkilogram of water per hour
CommonL/daylitre of condensate per day: Requires an explicit water-density basis

Definition

Moisture load is the rate at which water vapour must be removed from a defined space or process to maintain the selected humidity condition.

It is a mass-flow quantity, usually built from internal generation, outdoor-air ventilation and infiltration, wet materials, openings and process releases. The boundary, schedule and design condition belong to every load value.

Formula and variables

ṁ_w,load = Σ ṁ_w,source

Conditions: Steady-state mass balance for a defined control boundary. Each source term must use the same time basis and sign convention.

SymbolMeaningUnit
ṁ_w,loadwater-vapour removal rate required to hold the target conditionkg/s or kg/h
ṁ_w,sourcewater-vapour source rate crossing or generated within the boundarykg/s or kg/h

Relations and distinctions

Moisture load and latent load

Moisture load is a water mass rate. Latent load is the associated energy rate under a stated phase-change and reference-state basis.

Moisture load and rated capacity

Load belongs to the application; rated capacity belongs to equipment tested at stated conditions. Capacity must be evaluated against the actual load and operating state.

Engineering meaning

  1. Build the load by source and schedule before selecting dehumidification capacity.
  2. Use humidity-ratio and dry-air mass-flow balances for ventilation, infiltration and process-air contributions.

Common misconceptions

MisconceptionRoom volume and target RH are enough to determine moisture load.

Accurate explanationVolume affects transient storage, but steady load is governed by water-vapour sources, air exchange and the control boundary.

Application boundaries

  • A peak, average and startup moisture load can be different and must not be mixed.
  • The load calculation does not by itself include equipment derating, defrost time, air distribution or control reserve.

Supporting sources

  1. ASHRAE / SRC-ASHRAE-F25-CH18

    ASHRAE Handbook - Fundamentals, Chapter 18: Nonresidential Cooling and Heating Load Calculations ↗

    2025 SI edition / Chapter 18, Section 1, heat flow rates and moisture added to a space

    Supports: Moisture added within a space creates latent heat gain; At constant humidity ratio, water vapour must be removed at the rate it is added; Internal and outdoor-air sources must be included in load work
  2. ASHRAE / SRC-ASHRAE-F17-CH16

    ASHRAE Handbook - Fundamentals, Chapter 16: Ventilation and Infiltration ↗

    2017 SI edition / Chapter 16, air exchange effects on moisture and latent load, Equations 35 and related discussion

    Supports: Outdoor-air exchange can add or remove moisture; Humidity-ratio difference and airflow determine the air-exchange moisture contribution

Maintenance record

Moisture Load

Maintained by
Yakeclimate Engineering Team
Authoritative sources verified
August 3, 2026
Terminology checked
August 3, 2026
Last updated
August 3, 2026