Wet Bulb Calculator

Calculate thermodynamic wet-bulb temperature from dry bulb and RH or dew point, with local pressure for evaporative cooling, cooling-tower and coil-inlet reviews.

AIR CONDITIONS

Dry bulb −20…60°C (−4…140°F); pressure 60…110 kPa; supported RH 0.1…100%. Dew/frost point and wet bulb cannot exceed dry bulb. Subzero RH and frost point use the ice basis.

CALCULATED AIR STATE

Thermodynamic wet bulb
19.47 °C
Dew / frost point
16.70 °C
Humidity ratio · dry-air basis
11.90 g/kg
Absolute humidity · vapour density
13.82 g/m³

Example: 25°C dry bulb, 60% RH, 101.325 kPa.

01 / ENGINEERING USE

Use wet bulb as a process reference.

01

Evaporative cooling

Compare dry bulb with wet bulb to understand the available evaporative cooling potential. Actual leaving-air temperature also depends on equipment effectiveness and water conditions.

02

Cooling towers

Record entering-air wet bulb alongside water temperatures and flow. A wet-bulb calculation alone does not predict tower approach or heat-rejection capacity.

03

Coil inlet conditions

Pair dry bulb and wet bulb when reviewing HVAC coil duty. Add airflow and target leaving-air state before calculating moisture or energy removal.

02 / DEFINITIONS

Three different measurements and calculations

TermMeaning for this task
Thermodynamic wet bulbAn air-state property defined by adiabatic saturation at constant pressure. This is the calculated output here.
Ventilated psychrometer readingA wetted sensor exchanges heat and moisture with moving air. Wick condition, airflow, radiation and instrument corrections matter; the reading is not automatically identical to thermodynamic wet bulb.
WBGTWet-bulb globe temperature uses additional environmental measurements, including globe temperature. This calculator does not calculate WBGT or assess heat stress or health.

Calculation method and sources

Tdry + RH / Tdew + p → pᵥ → w → Twet

The shared air-property library solves the ASHRAE thermodynamic water/ice energy balance for wet bulb, following PsychroLib. At 25°C, 60% RH and 101.325 kPa, wet bulb is 19.47°C, dew point 16.70°C and humidity ratio 11.90 g/kg dry air.

ASHRAE Fundamentals (2017), Chapter 1, equations 33 / 35 · PsychroLib

Saturation pressure uses ice at or below 0.01°C and liquid water above; the wet-bulb energy balance changes phase at 0°C. Near freezing, check the instrument’s phase convention. Dew/frost-point input uses the same ice/water convention.

What this tool does not decide

It does not select cooling equipment, establish tower performance, calibrate a psychrometer, or determine worker exposure limits. Use measured airflow, actual equipment data and the required process conditions for equipment review.