Temperature and Humidity Measuring Devices: Types and How to Choose

Handheld thermo-hygrometers, wall displays, data loggers, transmitters and wireless sensors compared: accuracy, uses and what each can show, plus dew point and how to place them.

Written byYakeclimate Engineering TeamEngineering TeamReviewed by Jordan Shao, R&D Director

Quick answer: A temperature and humidity measuring device (thermo-hygrometer) reports air temperature and relative humidity together, and many also calculate dew point. Pick the type by the job: a handheld meter for spot checks and surveys, a wall display to watch a room, a data logger to record conditions over days or weeks, a transmitter (4–20 mA, 0–10 V or Modbus) to feed a control system, or wireless sensors to monitor many points remotely. Typical good accuracy is ±2–3 % RH and ±0.3–0.5 °C. Read temperature and RH together: the same air shows a different RH if it warms or cools.

Quick answer
  • Spot checks: handheld with dew point.
  • Records and audits: data logger.
  • Control and BMS: transmitter or networked sensor.

Types compared

TypeBest forTypical accuracyOutputWatch out for
Handheld thermo-hygrometerSurveys, troubleshooting, checking other sensors±2–3 % RH, ±0.3–0.5 °CDisplay; some log or connect to an appAllow time to settle; hand heat
Wall displayWatching a room, warehouse or office±3–5 % RHDisplayOften no record; placement on cold walls
Data loggerRecording conditions for audits, storage, transport, investigations±2–3 % RHDownload or cloudLogging interval; battery life
TransmitterFeeding a BMS, climate computer or dehumidifier controller±2 % RH or better4–20 mA, 0–10 V, ModbusWiring, power, calibration access
Wireless sensor networkMany points in large buildings, greenhouses, warehouses±2–3 % RHGateway and softwareSignal coverage; battery replacement
Reference instrument (chilled mirror, calibrated probe)Calibrating other sensorsDew point ±0.2 °C or betterLabCost; handling

NIST describes humidity measurement instruments and calibration (NIST, Hygrometers). For more on RH sensor accuracy and checking, see relative humidity gauges.

What the readings tell you

ReadingUse
TemperatureComfort, process limits, product temperature
RHMold and corrosion risk, product equilibrium moisture
Dew pointCondensation risk: compare with the coldest surface temperature
Absolute humidity (g/kg or g/m³)Comparing indoor and outdoor air; whether ventilation will dry a space

Example: a room at 22 °C and 55 % RH has a dew point of about 12.5 °C. A cold water pipe at 10 °C in that room will sweat even though 55 % RH sounds fine.

Placement

  • Where the decision applies: at product level in a warehouse, at canopy height in a greenhouse, near the coldest surface for condensation.
  • Away from sun, heaters, lights, air outlets and people.
  • Not on cold outside walls unless that is what you want to measure.
  • One per zone with different conditions.

See dew point sensor placement and industrial temperature and humidity monitoring.

Choosing by application

ApplicationDevice
Home, officeWall display or small logger
Warehouse, archive, storageWireless sensors or loggers with alarms
GreenhouseAspirated transmitters at canopy height; see greenhouse sensor placement
Water damage dryingHandheld with dew point and g/kg, plus moisture meter
Controlling dehumidifiersTransmitter in the controlled zone
Pharmaceutical, food, labCalibrated loggers with traceable certificates

Related: greenhouse sensor placement.

If readings show humidity staying high, see how to size a dehumidifier and our industrial dehumidifiers.

FAQ

Frequently asked questions

What device measures temperature and humidity?

A thermo-hygrometer: handheld, wall-mounted, logging or transmitter versions.

How accurate are temperature and humidity meters?

Good ones are about ±2–3 % RH and ±0.3–0.5 °C; cheap displays can be ±5 % RH or worse.

Should I measure dew point too?

Yes, whenever condensation matters. Dew point compared with surface temperature shows whether water will form.

How often should humidity sensors be calibrated?

Typically every 6–12 months, more often after exposure to condensation or contamination.

Sources

  • NIST, Hygrometers.
  • ASHRAE Handbook—Fundamentals, Measurement and instruments; Psychrometrics.

About the author

Yakeclimate Engineering Team

Engineering Team

Yakeclimate technical articles are prepared by the engineering team using inputs from product development, application review, manufacturing, testing, and project support.

View author profile

Reviewed by Jordan Shao, R&D Director

Continue reading

More on humidity science & engineering

Project evidence

Related case studies

Project support

Ready to turn the operating conditions into a project brief?

Use the project-input checklist to help our team review the environment, moisture load, interfaces, installation limits, and validation needs from one consistent brief.
Send project requirements