Rated Dehumidification Capacity
额定除湿量
Rated dehumidification capacity is the water-removal rate assigned to a dehumidifier under a named test method and specified operating conditions.
- Abbreviations
- MRC
- Aliases
- rated moisture removal capacity, dehumidifier capacity
QUANTITY, SYMBOL AND UNIT
Definition
Rated dehumidification capacity is the water-removal rate assigned to a dehumidifier under a named test method and specified operating conditions.
It may be expressed as kg/h, L/day or another mass-per-time unit. A valid comparison states the inlet temperature and humidity, airflow, pressure, operating mode, test duration and rating standard or manufacturer method.
Formula and variables
MRC = Δm_w / Δt Conditions: The removed water mass and elapsed time are measured under the named rating method, inlet conditions, airflow, pressure and operating mode.
| Symbol | Meaning | Unit |
|---|---|---|
MRC | rated moisture removal capacity | kg/h or L/day |
Δm_w | water removed during the rating interval | kg or L with density basis |
Δt | rating interval | h or day |
Relations and distinctions
Rated and actual capacity
Rated capacity belongs to a controlled test point. Actual capacity belongs to the project's entering state, controls, installation and time-averaged operation.
Capacity and moisture load
Capacity is equipment output; moisture load is the application's required removal rate. Selection must compare them on a compatible basis.
Engineering meaning
- Compare units only after normalizing the rating condition, time basis and included auxiliaries.
- Request performance data across the project's expected temperature and humidity range, including low-load or defrost operation where relevant.
Common misconceptions
MisconceptionA unit rated at 100 L/day will remove 100 litres every day in any room.
Accurate explanationThe rating applies only to its stated conditions; lower entering moisture, temperature, airflow or cycling can reduce field output.
Application boundaries
- Consumer, pool, DX outdoor-air and heat-regenerated desiccant ratings use different methods and scopes.
- Rated capacity does not by itself state energy use, outlet dew point, external static pressure, noise or control performance.
Supporting sources
-
ASHRAE / SRC-ASHRAE-TERMINOLOGY-M
ASHRAE Terminology: Moisture Removal Capacity ↗
/ Entry for moisture removal capacity
Supports: Moisture removal capacity is water-vapour mass removed from process air per unit time; The quantity is reported as a mass rate -
ASHRAE / SRC-ASHRAE-S20-CH25
ASHRAE Handbook - HVAC Systems and Equipment, Chapter 25: Mechanical Dehumidifiers and Related Components ↗
2020 SI edition / Chapter 25, capacity and performance rating discussion
Supports: Rated dehumidification capacity is determined under specified test conditions; Capacity changes with equipment type and operating condition; Low-temperature operation and defrost can alter delivered output -
ASHRAE / SRC-ASHRAE-STD139-2025-SCOPE
ANSI/ASHRAE Standard 139-2025 - Method of Testing for Rating Desiccant Dehumidifiers Utilizing Heat for the Regeneration Process ↗
2025 / ANSI/ASHRAE Standard 139-2025 title, purpose and public scope
Supports: Heat-regenerated desiccant dehumidifiers have a standardized moisture-removal-capacity test method; The standard scope is limited to stated desiccant equipment and atmospheric pressure; Ratings from one method must not be transferred outside its scope
Maintenance record
Rated Dehumidification Capacity
- Maintained by
- Yakeclimate Engineering Team
- Authoritative sources verified
- August 3, 2026
- Terminology checked
- August 3, 2026
- Last updated
- August 3, 2026