EKS-HUM-037 / Dehumidification technology and performance

Rated Dehumidification Capacity

额定除湿量

Rated dehumidification capacity is the water-removal rate assigned to a dehumidifier under a named test method and specified operating conditions.

Abbreviations
MRC
Aliases
rated moisture removal capacity, dehumidifier capacity

QUANTITY, SYMBOL AND UNIT

Quantity / objectRated moisture removal capacity
SymbolMRC, ṁ_w,rated
SIkg/hkilogram of water per hour
CommonL/daylitre per day: Requires an explicit water-density and time basis
IPpt/daypint per day

Definition

Rated dehumidification capacity is the water-removal rate assigned to a dehumidifier under a named test method and specified operating conditions.

It may be expressed as kg/h, L/day or another mass-per-time unit. A valid comparison states the inlet temperature and humidity, airflow, pressure, operating mode, test duration and rating standard or manufacturer method.

Formula and variables

MRC = Δm_w / Δt

Conditions: The removed water mass and elapsed time are measured under the named rating method, inlet conditions, airflow, pressure and operating mode.

SymbolMeaningUnit
MRCrated moisture removal capacitykg/h or L/day
Δm_wwater removed during the rating intervalkg or L with density basis
Δtrating intervalh or day

Relations and distinctions

Rated and actual capacity

Rated capacity belongs to a controlled test point. Actual capacity belongs to the project's entering state, controls, installation and time-averaged operation.

Capacity and moisture load

Capacity is equipment output; moisture load is the application's required removal rate. Selection must compare them on a compatible basis.

Engineering meaning

  1. Compare units only after normalizing the rating condition, time basis and included auxiliaries.
  2. Request performance data across the project's expected temperature and humidity range, including low-load or defrost operation where relevant.

Common misconceptions

MisconceptionA unit rated at 100 L/day will remove 100 litres every day in any room.

Accurate explanationThe rating applies only to its stated conditions; lower entering moisture, temperature, airflow or cycling can reduce field output.

Application boundaries

  • Consumer, pool, DX outdoor-air and heat-regenerated desiccant ratings use different methods and scopes.
  • Rated capacity does not by itself state energy use, outlet dew point, external static pressure, noise or control performance.

Supporting sources

  1. ASHRAE / SRC-ASHRAE-TERMINOLOGY-M

    ASHRAE Terminology: Moisture Removal Capacity ↗

    / Entry for moisture removal capacity

    Supports: Moisture removal capacity is water-vapour mass removed from process air per unit time; The quantity is reported as a mass rate
  2. ASHRAE / SRC-ASHRAE-S20-CH25

    ASHRAE Handbook - HVAC Systems and Equipment, Chapter 25: Mechanical Dehumidifiers and Related Components ↗

    2020 SI edition / Chapter 25, capacity and performance rating discussion

    Supports: Rated dehumidification capacity is determined under specified test conditions; Capacity changes with equipment type and operating condition; Low-temperature operation and defrost can alter delivered output
  3. ASHRAE / SRC-ASHRAE-STD139-2025-SCOPE

    ANSI/ASHRAE Standard 139-2025 - Method of Testing for Rating Desiccant Dehumidifiers Utilizing Heat for the Regeneration Process ↗

    2025 / ANSI/ASHRAE Standard 139-2025 title, purpose and public scope

    Supports: Heat-regenerated desiccant dehumidifiers have a standardized moisture-removal-capacity test method; The standard scope is limited to stated desiccant equipment and atmospheric pressure; Ratings from one method must not be transferred outside its scope