Dehumidification technology and performance
Entering-air Condition
进风工况
Entering-air condition is the stated thermodynamic and flow state of the air at a defined equipment or process inlet.
- Abbreviations
- EAC
- Aliases
- inlet-air condition, entering condition
QUANTITY, SYMBOL AND UNIT
Definition
Entering-air condition is the stated thermodynamic and flow state of the air at a defined equipment or process inlet.
For dehumidification it normally includes dry-bulb temperature and at least one moisture property, and may also require pressure, airflow and the exact measurement location. Capacity data are meaningful only when the entering condition and test basis are known.
Relations and distinctions
Entering and room condition
Room air may mix, heat or cool before reaching the equipment inlet, so a room sensor is not automatically the entering-air state.
Entering and rating condition
An entering condition is any stated inlet state; a rating condition is a defined test point used to assign performance.
Engineering meaning
- Compare required performance with data at matching inlet temperature, moisture state, airflow and pressure.
- Name the inlet plane and sensor locations when commissioning or diagnosing capacity.
Common misconceptions
MisconceptionA daily room RH average is enough to select dehumidification capacity.
Accurate explanationEquipment responds to the coincident air state and flow at its inlet, including peaks and changes caused by mixing or duct conditions.
Application boundaries
- The term does not specify one standard industrial rating point.
- Entering-air condition alone does not include the moisture load, leaving-air target, external static pressure or all auxiliary operating limits.
Supporting sources
-
ASHRAE / SRC-ASHRAE-S20-CH25
ASHRAE Handbook - HVAC Systems and Equipment, Chapter 25: Mechanical Dehumidifiers and Related Components ↗
2020 SI edition / Chapter 25, dehumidification process points, performance and entering-air discussions
Supports: Dehumidifier performance depends on the condition of air crossing the dehumidifying coil; Entering-air dry-bulb and moisture state affect capacity and operating point; Outdoor-air mixing or heat recovery can change the entering state and performance
Maintenance record
Entering-air Condition
- Maintained by
- Yakeclimate Engineering Team
- Authoritative sources verified
- August 3, 2026
- Terminology checked
- August 3, 2026
- Last updated
- August 3, 2026
- Term ID
- EKS-HUM-075